MODEL | MP RT 6k | MP RT 10k |
Capacity | 6000VA/ 5400W | 10000VA/ 9000W |
INPUT | |
Nominal voltage | 208/220/230/240Vac |
Input voltage range | 110~286Vac |
Frequency range | 40~70Hz (50/60Hz Auto-Sensing) |
Power factor | ≥0.99 |
| Max.voltage:220V: 25% (Optional 10%, 15%, 20%) 230V: 20% (Optional 10%, 15%, 20%) |
Bypass voltage range | 240V: 15% (Optional 10%) |
| Min.voltage:-45% (Optional-20%,-30%) |
OUTPUT | |
Output voltage | 208/220/230/240Vac |
Power factor | 0.9 |
Voltage regulation | ±1% |
Output frequency | Line Mode | ±1%/±2%±/±4%/±5%/±10% of the rated frequency (Optional) |
Bat. Mode | (50/60±0.1%)Hz |
Crest factor | 3:01 |
Harmonic distortion (THDv) | ≤2% Linear load |
≤5% Non linear load |
Transfer time | AC mode to Bat.Mode | 0ms |
Inverter to Bypass | 0ms |
Output waveform | Pure Sinewave |
Overload | Line Mode | Load≤110% last 60min; ≤125% last 10min; ≤150% last 1min; >150% turn to bypass mode immediately |
Bypass Mode | 40A (Breaker) | 63A (Breaker) |
Efficiency | 94% |
BATTERY | |
Battery voltage | ±96/±108/±120Vdc (Adjustable) | ±120Vdc | ±96/±108/±120Vdc (Adjustable) | ±120Vdc |
Capacity (Standard unit) | 9Ah/12V (7Ah/12V optional) |
Typical recharging time | 6~8 hours (to 90% of full capacity) |
Charging current | 1A (Standard unit); Long run unit Max.current 10A (Charging current can be set according to battery capacity) |
INDICATORS | |
LED display | Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault |
LCD display | Input voltage,Input frequency,Output voltage,Output frequency,Load percentage, |
Battery voltage,Inner temperature& Remaining battery backup time |
ALARM | |
Battery mode | Beeping every 4 seconds |
Battery low | Beeping every second |
Overload | Beeping twice every second |
Fault | Continously beeping |
PHYSICAL | |
Dimension W x D×H (mm) | 440 x 625 x 86.5 |
Net weight (kg) | 16 | 18 |
ENVIRONMENT | |
Operating temperature | 0℃~40℃ |
Storage temperature | -25℃~55℃ |
Humidity range | 20~95%RH @ 0~40℃ (Non condensing) |
Altitude | <1500m,derating required when>1500m |
Noise level | <55db at 1 Meter | <58db at 1 Meter |
STANDARDS | |
Safety | IEC/EN62040-1,IEC/EN62477-1 |
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |