KSTAR
KSTAR UPS UA60 (KSTAR UPS UA60)
Model | UA40 | UA60 | UA80 | UA100 | UA120 | UA150 | UA200 | UA240 | UA300 |
Capacity (VA/Watts) | 400 / 240 | 600/ 360 | 800 /480 | 1000/ 600 | 1200/ 720 | 1500 / 900 | 2000 / 1200 | 2400/ 1440 | 3000 / 1800 |
INPUT | |||||||||
Nominal Input Voltage | 110/120Vac or 220/230/240 Vac | ||||||||
Operating Voltage Range | 81-145Vac/162-290 Vac | ||||||||
Operating FrequencyRange | 50/60 Hz (1±10%) | ||||||||
OUTPUT | |||||||||
Output Voltage range (Batt. Mode) | Simulated Sinewave at nominal voltage ±10% | ||||||||
Frequency Range (Batt. Mode) | 50 Hz or 60 Hz ± 1 Hz | ||||||||
Transfer Time | Typical 2-6 ms, 10ms max. | ||||||||
BATTERY | |||||||||
Battery Type & Number | 12V/4.5Ah x 1 | 12V/7Ah x 1 | 12V/9Ah x 1 | 12V/7Ah x 2 | 12V/7Ah x2 | 12V/9Ah x 2 | 12V/9Ah x 2 | 12V/7Ah x 4 | 12V/9Ah x 4 |
Typical Recharge Time | 6-8 hours ( To 90% capacity) | ||||||||
PROTECTION | |||||||||
Full Protection | Overload and overcharge protection | ||||||||
INDICATORS | |||||||||
Indicators | AC Mode, Battery Mode, Load Level, Battery Level | AC Mode, Battery Mode, Load Level, Battery Level, Input Voltage, Output Voltage, Overload, Fault, Battery Low | |||||||
ALARM | |||||||||
Battery Mode | Sounding every 10 seconds | ||||||||
Battery Low | Sounding every second | ||||||||
Overload | Sounding every 0.5 second | ||||||||
Battery Replacement Alarm | Sounding every 2 seconds | ||||||||
Fault | Continuously sounding | ||||||||
Management | |||||||||
USB & RS-232 port(Optional) | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC | ||||||||
Environment | |||||||||
Operating Temperature | 0- 40°C | ||||||||
Humidity Range | 0-95 % (Non-condensing) | ||||||||
Noise Level | <40db (1 meter from surface) | ||||||||
PHYSICAL | |||||||||
Dimension, W x D x H (mm) | 101×298×142 | 149.3×338×162 | 158×380×198 | 144×432.5×207 | |||||
Net Weight (kg) | 3.55 | 4.25 | 4.9 | 7.8 | 8 | 11.1 | 11.5 | 20 | 23 |
STANDARDS | |||||||||
Safety | IEC/EN62040-1;IEC/EN60950-1 | ||||||||
EMC | IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4;IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
600VA | 360 WATTS | Line Interactive | 1 x 12v 7ah
KSTAR UPS UA120 (KSTAR UPS UA120)
Model | UA40 | UA60 | UA80 | UA100 | UA120 | UA150 | UA200 | UA240 | UA300 |
Capacity (VA/Watts) | 400 / 240 | 600/ 360 | 800 /480 | 1000/ 600 | 1200/ 720 | 1500 / 900 | 2000 / 1200 | 2400/ 1440 | 3000 / 1800 |
INPUT | |||||||||
Nominal Input Voltage | 110/120Vac or 220/230/240 Vac | ||||||||
Operating Voltage Range | 81-145Vac/162-290 Vac | ||||||||
Operating FrequencyRange | 50/60 Hz (1±10%) | ||||||||
OUTPUT | |||||||||
Output Voltage range (Batt. Mode) | Simulated Sinewave at nominal voltage ±10% | ||||||||
Frequency Range (Batt. Mode) | 50 Hz or 60 Hz ± 1 Hz | ||||||||
Transfer Time | Typical 2-6 ms, 10ms max. | ||||||||
BATTERY | |||||||||
Battery Type & Number | 12V/4.5Ah x 1 | 12V/7Ah x 1 | 12V/9Ah x 1 | 12V/7Ah x 2 | 12V/7Ah x2 | 12V/9Ah x 2 | 12V/9Ah x 2 | 12V/7Ah x 4 | 12V/9Ah x 4 |
Typical Recharge Time | 6-8 hours ( To 90% capacity) | ||||||||
PROTECTION | |||||||||
Full Protection | Overload and overcharge protection | ||||||||
INDICATORS | |||||||||
Indicators | AC Mode, Battery Mode, Load Level, Battery Level | AC Mode, Battery Mode, Load Level, Battery Level, Input Voltage, Output Voltage, Overload, Fault, Battery Low | |||||||
ALARM | |||||||||
Battery Mode | Sounding every 10 seconds | ||||||||
Battery Low | Sounding every second | ||||||||
Overload | Sounding every 0.5 second | ||||||||
Battery Replacement Alarm | Sounding every 2 seconds | ||||||||
Fault | Continuously sounding | ||||||||
Management | |||||||||
USB & RS-232 port(Optional) | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC | ||||||||
Environment | |||||||||
Operating Temperature | 0- 40°C | ||||||||
Humidity Range | 0-95 % (Non-condensing) | ||||||||
Noise Level | <40db (1 meter from surface) | ||||||||
PHYSICAL | |||||||||
Dimension, W x D x H (mm) | 101×298×142 | 149.3×338×162 | 158×380×198 | 144×432.5×207 | |||||
Net Weight (kg) | 3.55 | 4.25 | 4.9 | 7.8 | 8 | 11.1 | 11.5 | 20 | 23 |
STANDARDS | |||||||||
Safety | IEC/EN62040-1;IEC/EN60950-1 | ||||||||
EMC | IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4;IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
1200VA 1.2KVA | 720 WATTS | Line Interactive | 2 x 12v 7ah
KSTAR UPS UA200 (KSTAR UPS UA200)
Model | UA40 | UA60 | UA80 | UA100 | UA120 | UA150 | UA200 | UA240 | UA300 |
Capacity (VA/Watts) | 400 / 240 | 600/ 360 | 800 /480 | 1000/ 600 | 1200/ 720 | 1500 / 900 | 2000 / 1200 | 2400/ 1440 | 3000 / 1800 |
INPUT | |||||||||
Nominal Input Voltage | 110/120Vac or 220/230/240 Vac | ||||||||
Operating Voltage Range | 81-145Vac/162-290 Vac | ||||||||
Operating FrequencyRange | 50/60 Hz (1±10%) | ||||||||
OUTPUT | |||||||||
Output Voltage range (Batt. Mode) | Simulated Sinewave at nominal voltage ±10% | ||||||||
Frequency Range (Batt. Mode) | 50 Hz or 60 Hz ± 1 Hz | ||||||||
Transfer Time | Typical 2-6 ms, 10ms max. | ||||||||
BATTERY | |||||||||
Battery Type & Number | 12V/4.5Ah x 1 | 12V/7Ah x 1 | 12V/9Ah x 1 | 12V/7Ah x 2 | 12V/7Ah x2 | 12V/9Ah x 2 | 12V/9Ah x 2 | 12V/7Ah x 4 | 12V/9Ah x 4 |
Typical Recharge Time | 6-8 hours ( To 90% capacity) | ||||||||
PROTECTION | |||||||||
Full Protection | Overload and overcharge protection | ||||||||
INDICATORS | |||||||||
Indicators | AC Mode, Battery Mode, Load Level, Battery Level | AC Mode, Battery Mode, Load Level, Battery Level, Input Voltage, Output Voltage, Overload, Fault, Battery Low | |||||||
ALARM | |||||||||
Battery Mode | Sounding every 10 seconds | ||||||||
Battery Low | Sounding every second | ||||||||
Overload | Sounding every 0.5 second | ||||||||
Battery Replacement Alarm | Sounding every 2 seconds | ||||||||
Fault | Continuously sounding | ||||||||
Management | |||||||||
USB & RS-232 port(Optional) | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC | ||||||||
Environment | |||||||||
Operating Temperature | 0- 40°C | ||||||||
Humidity Range | 0-95 % (Non-condensing) | ||||||||
Noise Level | <40db (1 meter from surface) | ||||||||
PHYSICAL | |||||||||
Dimension, W x D x H (mm) | 101×298×142 | 149.3×338×162 | 158×380×198 | 144×432.5×207 | |||||
Net Weight (kg) | 3.55 | 4.25 | 4.9 | 7.8 | 8 | 11.1 | 11.5 | 20 | 23 |
STANDARDS | |||||||||
Safety | IEC/EN62040-1;IEC/EN60950-1 | ||||||||
EMC | IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4;IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
2000VA 2KVA | 1200 WATTS | Line Interactive | 2 x 12v 9ah
KSTAR UPS MP RT 1KS (KSTAR UPS MP RT 1KS)
Technical Specification
MODEL | MP RT 1k H | MP RT 1k S | MP RT 2k H | MP RT 2k S | MP RT 3k H | MP RT 3k S | ||||||
Capacity | 1000VA/ 900W | 2000VA/ 1800W | 3000VA/ 2700W | |||||||||
INPUT | ||||||||||||
Nominal voltage | 208/220/230/240Vac | |||||||||||
Input voltage range | 110~300Vac (176~280Vac @ 100% load) | |||||||||||
Frequency range | 40~70Hz (50/60Hz Auto-Sensing) | |||||||||||
Power factor | ≥0.99 | |||||||||||
OUTPUT | ||||||||||||
Output voltage | 208/220/230/240Vac | |||||||||||
Power factor | 0.9 | |||||||||||
Voltage regulation | ±1% | |||||||||||
Output frequency | Line Mode | 46~54Hz or 56~64Hz | ||||||||||
Bat. Mode | (50/60±0.1%)Hz | |||||||||||
Crest factor | 3:01 | |||||||||||
Harmonic distortion (THDv) | ≤3% Linear load | |||||||||||
≤5% Non linear load | ||||||||||||
Transfer time | AC mode to Bat.Mode | 0ms | ||||||||||
Inverter to Bypass | 4ms (Typical) | |||||||||||
Output waveform | Pure Sinewave | |||||||||||
EFFICIENCY | ||||||||||||
AC mode | 89% | 91% | 92% | |||||||||
Battery mode | 85% | 87% | 88% | |||||||||
BATTERY | ||||||||||||
Battery number | 2 | 3 | 2 | 3 | 4 | 6 | 4 | 6 | 6 | 8 | 6 | |
Capacity (Standard unit) | 9Ah/12V | |||||||||||
Typical recharging time | 4 hours (to 90% of full capacity) | |||||||||||
Charging voltage | 27.4Vdc±1% | 41.1Vdc±1% | 27.4Vdc±1% | 41.1Vdc±1% | 54.8Vdc±1% | 82.2Vdc±1% | 54.8Vdc±1% | 82.2Vdc±1% | 82.2Vdc±1% | 109.6Vdc±1% | 82.2Vdc±1% | |
Charging current (Max) | 6A/12A | 1A | 6A/12A | 1A | 6A/12A | 1A | ||||||
INDICATORS | ||||||||||||
LED display | Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault | |||||||||||
LCD display | Input voltage,Input frequency,Output voltage,Output frequency,Load percentage, | |||||||||||
Battery voltage,Inner temperature& Remaining battery backup time | ||||||||||||
ALARM | ||||||||||||
Battery mode | Beeping every 4 seconds | |||||||||||
Battery low | Beeping every second | |||||||||||
Overload | Beeping twice every second | |||||||||||
Fault | Continously beeping | |||||||||||
PHYSICAL | ||||||||||||
Dimension W x D×H (mm) | 440 x 325x 86.5 | 440 x 460 x 86.5 | 440 x 600 x 86.5 | 440 x 460 x 86.5 | 440 x 600 x 86.5 | |||||||
Net weight (kg) | 5.6 | 11.3 | 14 | 10.5 | 19.5 | 25 | 11 | 26 | ||||
ENVIRONMENT | ||||||||||||
Operating temperature | 0℃~40℃ | |||||||||||
Storage temperature | -25℃~55℃ | |||||||||||
Humidity range | 20~95%RH @ 0~40℃ (Non condensing) | |||||||||||
Altitude | <1500m,derating required when>1500m | |||||||||||
Noise level | <50db at 1 Meter | |||||||||||
STANDARDS | ||||||||||||
Safety | IEC/EN62040-1,IEC/EN62477-1 | |||||||||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
1000VA 1KVA | 900 WATTS | Online | 2 x 12v 9ah
KSTAR UPS MP RT 2KS (KSTAR UPS MP RT 2KS)
Technical Specification
MODEL | MP RT 1k H | MP RT 1k S | MP RT 2k H | MP RT 2k S | MP RT 3k H | MP RT 3k S | ||||||
Capacity | 1000VA/ 900W | 2000VA/ 1800W | 3000VA/ 2700W | |||||||||
INPUT | ||||||||||||
Nominal voltage | 208/220/230/240Vac | |||||||||||
Input voltage range | 110~300Vac (176~280Vac @ 100% load) | |||||||||||
Frequency range | 40~70Hz (50/60Hz Auto-Sensing) | |||||||||||
Power factor | ≥0.99 | |||||||||||
OUTPUT | ||||||||||||
Output voltage | 208/220/230/240Vac | |||||||||||
Power factor | 0.9 | |||||||||||
Voltage regulation | ±1% | |||||||||||
Output frequency | Line Mode | 46~54Hz or 56~64Hz | ||||||||||
Bat. Mode | (50/60±0.1%)Hz | |||||||||||
Crest factor | 3:01 | |||||||||||
Harmonic distortion (THDv) | ≤3% Linear load | |||||||||||
≤5% Non linear load | ||||||||||||
Transfer time | AC mode to Bat.Mode | 0ms | ||||||||||
Inverter to Bypass | 4ms (Typical) | |||||||||||
Output waveform | Pure Sinewave | |||||||||||
EFFICIENCY | ||||||||||||
AC mode | 89% | 91% | 92% | |||||||||
Battery mode | 85% | 87% | 88% | |||||||||
BATTERY | ||||||||||||
Battery number | 2 | 3 | 2 | 3 | 4 | 6 | 4 | 6 | 6 | 8 | 6 | |
Capacity (Standard unit) | 9Ah/12V | |||||||||||
Typical recharging time | 4 hours (to 90% of full capacity) | |||||||||||
Charging voltage | 27.4Vdc±1% | 41.1Vdc±1% | 27.4Vdc±1% | 41.1Vdc±1% | 54.8Vdc±1% | 82.2Vdc±1% | 54.8Vdc±1% | 82.2Vdc±1% | 82.2Vdc±1% | 109.6Vdc±1% | 82.2Vdc±1% | |
Charging current (Max) | 6A/12A | 1A | 6A/12A | 1A | 6A/12A | 1A | ||||||
INDICATORS | ||||||||||||
LED display | Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault | |||||||||||
LCD display | Input voltage,Input frequency,Output voltage,Output frequency,Load percentage, | |||||||||||
Battery voltage,Inner temperature& Remaining battery backup time | ||||||||||||
ALARM | ||||||||||||
Battery mode | Beeping every 4 seconds | |||||||||||
Battery low | Beeping every second | |||||||||||
Overload | Beeping twice every second | |||||||||||
Fault | Continously beeping | |||||||||||
PHYSICAL | ||||||||||||
Dimension W x D×H (mm) | 440 x 325x 86.5 | 440 x 460 x 86.5 | 440 x 600 x 86.5 | 440 x 460 x 86.5 | 440 x 600 x 86.5 | |||||||
Net weight (kg) | 5.6 | 11.3 | 14 | 10.5 | 19.5 | 25 | 11 | 26 | ||||
ENVIRONMENT | ||||||||||||
Operating temperature | 0℃~40℃ | |||||||||||
Storage temperature | -25℃~55℃ | |||||||||||
Humidity range | 20~95%RH @ 0~40℃ (Non condensing) | |||||||||||
Altitude | <1500m,derating required when>1500m | |||||||||||
Noise level | <50db at 1 Meter | |||||||||||
STANDARDS | ||||||||||||
Safety | IEC/EN62040-1,IEC/EN62477-1 | |||||||||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
2000VA 2KVA | 1800 WATTS | Online | 4 x 12v 9ah
KSTAR UPS MP RT 3KS (KSTAR UPS MP RT 3KS)
Technical Specification
MODEL | MP RT 1k H | MP RT 1k S | MP RT 2k H | MP RT 2k S | MP RT 3k H | MP RT 3k S | ||||||
Capacity | 1000VA/ 900W | 2000VA/ 1800W | 3000VA/ 2700W | |||||||||
INPUT | ||||||||||||
Nominal voltage | 208/220/230/240Vac | |||||||||||
Input voltage range | 110~300Vac (176~280Vac @ 100% load) | |||||||||||
Frequency range | 40~70Hz (50/60Hz Auto-Sensing) | |||||||||||
Power factor | ≥0.99 | |||||||||||
OUTPUT | ||||||||||||
Output voltage | 208/220/230/240Vac | |||||||||||
Power factor | 0.9 | |||||||||||
Voltage regulation | ±1% | |||||||||||
Output frequency | Line Mode | 46~54Hz or 56~64Hz | ||||||||||
Bat. Mode | (50/60±0.1%)Hz | |||||||||||
Crest factor | 3:01 | |||||||||||
Harmonic distortion (THDv) | ≤3% Linear load | |||||||||||
≤5% Non linear load | ||||||||||||
Transfer time | AC mode to Bat.Mode | 0ms | ||||||||||
Inverter to Bypass | 4ms (Typical) | |||||||||||
Output waveform | Pure Sinewave | |||||||||||
EFFICIENCY | ||||||||||||
AC mode | 89% | 91% | 92% | |||||||||
Battery mode | 85% | 87% | 88% | |||||||||
BATTERY | ||||||||||||
Battery number | 2 | 3 | 2 | 3 | 4 | 6 | 4 | 6 | 6 | 8 | 6 | |
Capacity (Standard unit) | 9Ah/12V | |||||||||||
Typical recharging time | 4 hours (to 90% of full capacity) | |||||||||||
Charging voltage | 27.4Vdc±1% | 41.1Vdc±1% | 27.4Vdc±1% | 41.1Vdc±1% | 54.8Vdc±1% | 82.2Vdc±1% | 54.8Vdc±1% | 82.2Vdc±1% | 82.2Vdc±1% | 109.6Vdc±1% | 82.2Vdc±1% | |
Charging current (Max) | 6A/12A | 1A | 6A/12A | 1A | 6A/12A | 1A | ||||||
INDICATORS | ||||||||||||
LED display | Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault | |||||||||||
LCD display | Input voltage,Input frequency,Output voltage,Output frequency,Load percentage, | |||||||||||
Battery voltage,Inner temperature& Remaining battery backup time | ||||||||||||
ALARM | ||||||||||||
Battery mode | Beeping every 4 seconds | |||||||||||
Battery low | Beeping every second | |||||||||||
Overload | Beeping twice every second | |||||||||||
Fault | Continously beeping | |||||||||||
PHYSICAL | ||||||||||||
Dimension W x D×H (mm) | 440 x 325x 86.5 | 440 x 460 x 86.5 | 440 x 600 x 86.5 | 440 x 460 x 86.5 | 440 x 600 x 86.5 | |||||||
Net weight (kg) | 5.6 | 11.3 | 14 | 10.5 | 19.5 | 25 | 11 | 26 | ||||
ENVIRONMENT | ||||||||||||
Operating temperature | 0℃~40℃ | |||||||||||
Storage temperature | -25℃~55℃ | |||||||||||
Humidity range | 20~95%RH @ 0~40℃ (Non condensing) | |||||||||||
Altitude | <1500m,derating required when>1500m | |||||||||||
Noise level | <50db at 1 Meter | |||||||||||
STANDARDS | ||||||||||||
Safety | IEC/EN62040-1,IEC/EN62477-1 | |||||||||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
3000VA 3KVA | 2700 WATTS | Online | 6 x 12v 9ah
KSTAR UPS MP RT 6K (KSTAR UPS MP RT 6K)
MODEL | MP RT 6k | MP RT 10k | |||
Capacity | 6000VA/ 5400W | 10000VA/ 9000W | |||
INPUT | |||||
Nominal voltage | 208/220/230/240Vac | ||||
Input voltage range | 110~286Vac | ||||
Frequency range | 40~70Hz (50/60Hz Auto-Sensing) | ||||
Power factor | ≥0.99 | ||||
Max.voltage:220V: 25% (Optional 10%, 15%, 20%) 230V: 20% (Optional 10%, 15%, 20%) | |||||
Bypass voltage range | 240V: 15% (Optional 10%) | ||||
Min.voltage:-45% (Optional-20%,-30%) | |||||
OUTPUT | |||||
Output voltage | 208/220/230/240Vac | ||||
Power factor | 0.9 | ||||
Voltage regulation | ±1% | ||||
Output frequency | Line Mode | ±1%/±2%±/±4%/±5%/±10% of the rated frequency (Optional) | |||
Bat. Mode | (50/60±0.1%)Hz | ||||
Crest factor | 3:01 | ||||
Harmonic distortion (THDv) | ≤2% Linear load | ||||
≤5% Non linear load | |||||
Transfer time | AC mode to Bat.Mode | 0ms | |||
Inverter to Bypass | 0ms | ||||
Output waveform | Pure Sinewave | ||||
Overload | Line Mode | Load≤110% last 60min; ≤125% last 10min; ≤150% last 1min; >150% turn to bypass mode immediately | |||
Bypass Mode | 40A (Breaker) | 63A (Breaker) | |||
Efficiency | 94% | ||||
BATTERY | |||||
Battery voltage | ±96/±108/±120Vdc (Adjustable) | ±120Vdc | ±96/±108/±120Vdc (Adjustable) | ±120Vdc | |
Capacity (Standard unit) | 9Ah/12V (7Ah/12V optional) | ||||
Typical recharging time | 6~8 hours (to 90% of full capacity) | ||||
Charging current | 1A (Standard unit); Long run unit Max.current 10A (Charging current can be set according to battery capacity) | ||||
INDICATORS | |||||
LED display | Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault | ||||
LCD display | Input voltage,Input frequency,Output voltage,Output frequency,Load percentage, | ||||
Battery voltage,Inner temperature& Remaining battery backup time | |||||
ALARM | |||||
Battery mode | Beeping every 4 seconds | ||||
Battery low | Beeping every second | ||||
Overload | Beeping twice every second | ||||
Fault | Continously beeping | ||||
PHYSICAL | |||||
Dimension W x D×H (mm) | 440 x 625 x 86.5 | ||||
Net weight (kg) | 16 | 18 | |||
ENVIRONMENT | |||||
Operating temperature | 0℃~40℃ | ||||
Storage temperature | -25℃~55℃ | ||||
Humidity range | 20~95%RH @ 0~40℃ (Non condensing) | ||||
Altitude | <1500m,derating required when>1500m | ||||
Noise level | <55db at 1 Meter | <58db at 1 Meter | |||
STANDARDS | |||||
Safety | IEC/EN62040-1,IEC/EN62477-1 | ||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
6000VA 6KVA | 5400 WATTS | Online | No Battery
KSTAR UPS MP RT 10K (KSTAR UPS MP RT 10K)
MODEL | MP RT 6k | MP RT 10k | |||
Capacity | 6000VA/ 5400W | 10000VA/ 9000W | |||
INPUT | |||||
Nominal voltage | 208/220/230/240Vac | ||||
Input voltage range | 110~286Vac | ||||
Frequency range | 40~70Hz (50/60Hz Auto-Sensing) | ||||
Power factor | ≥0.99 | ||||
Max.voltage:220V: 25% (Optional 10%, 15%, 20%) 230V: 20% (Optional 10%, 15%, 20%) | |||||
Bypass voltage range | 240V: 15% (Optional 10%) | ||||
Min.voltage:-45% (Optional-20%,-30%) | |||||
OUTPUT | |||||
Output voltage | 208/220/230/240Vac | ||||
Power factor | 0.9 | ||||
Voltage regulation | ±1% | ||||
Output frequency | Line Mode | ±1%/±2%±/±4%/±5%/±10% of the rated frequency (Optional) | |||
Bat. Mode | (50/60±0.1%)Hz | ||||
Crest factor | 3:01 | ||||
Harmonic distortion (THDv) | ≤2% Linear load | ||||
≤5% Non linear load | |||||
Transfer time | AC mode to Bat.Mode | 0ms | |||
Inverter to Bypass | 0ms | ||||
Output waveform | Pure Sinewave | ||||
Overload | Line Mode | Load≤110% last 60min; ≤125% last 10min; ≤150% last 1min; >150% turn to bypass mode immediately | |||
Bypass Mode | 40A (Breaker) | 63A (Breaker) | |||
Efficiency | 94% | ||||
BATTERY | |||||
Battery voltage | ±96/±108/±120Vdc (Adjustable) | ±120Vdc | ±96/±108/±120Vdc (Adjustable) | ±120Vdc | |
Capacity (Standard unit) | 9Ah/12V (7Ah/12V optional) | ||||
Typical recharging time | 6~8 hours (to 90% of full capacity) | ||||
Charging current | 1A (Standard unit); Long run unit Max.current 10A (Charging current can be set according to battery capacity) | ||||
INDICATORS | |||||
LED display | Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault | ||||
LCD display | Input voltage,Input frequency,Output voltage,Output frequency,Load percentage, | ||||
Battery voltage,Inner temperature& Remaining battery backup time | |||||
ALARM | |||||
Battery mode | Beeping every 4 seconds | ||||
Battery low | Beeping every second | ||||
Overload | Beeping twice every second | ||||
Fault | Continously beeping | ||||
PHYSICAL | |||||
Dimension W x D×H (mm) | 440 x 625 x 86.5 | ||||
Net weight (kg) | 16 | 18 | |||
ENVIRONMENT | |||||
Operating temperature | 0℃~40℃ | ||||
Storage temperature | -25℃~55℃ | ||||
Humidity range | 20~95%RH @ 0~40℃ (Non condensing) | ||||
Altitude | <1500m,derating required when>1500m | ||||
Noise level | <55db at 1 Meter | <58db at 1 Meter | |||
STANDARDS | |||||
Safety | IEC/EN62040-1,IEC/EN62477-1 | ||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
10000VA 10KVA | 9000 WATTS | Online | No Battery